Power System’stransmission Line Relaying Improvement Using Discrete Wavelet Transform S. Mohaddeesh*, S. Taj Mahaboob** *(PG Scholar, DE & CS, JNTUACE Pulivendula, Andhra Pradesh) ** (Asst. Professor, Dept. of ECE, JNTUACE Pulivendula, Andhra Pradesh) ABSTRACT Transmission line is a path between the generating station and load(Industries & Domestic). These lines are several kilometres and always attracted towards faults. These Faults are Phase to Ground (P-G), Phase to Phase (P-P), Phase to Phase to Ground (P-P-G) and Symmetrical Fault (P-P-PP-P-P-G).In order to protect the power system, faults should be cleared within stipulated time. Relay plays a key role in power system protection, before employing them in system, their parameters should be pre-determined.The proposed system uses Discrete Wavelet Transform to determine the fault levels in power system. It is used to extract the hidden factors i.e. Transients, from the faulty current signals by performing decomposition at different levels. Test system is modelled and fault signals are imported to workspace and test the reliability of the algorithm. The proposed system modelled in MATLABSIMULINK to detect, classify and locate all the possible faults in the transmission line in the power system which are nothing but parameters of relays. 
Keywords – Discrete Wavelet Transform, Faults, Relay Parameters, Transients, Transmission Line. 
I. INTRODUCTION 
Electricity is very important component to universe. Power System is a system which generate electricity and dispatch to the loads these are generally industries and households. Power System consists Generating stations, Transmission lines and Load Centres. Transmission line interconnects the generating station to different load centres, they run over several kilometres and fascinated to faults, and to maintain continuity of operation we should clear the faults within short period. Relay plays main role in protection of transmission line, and assimilated to detect the abnormal condition in the system which notice faults and isolate the faulty part from the power system with negligible disturbance in the system. There are several relaying schemes are available they are 
 Overcurrent relaying scheme. 
 Differential relaying scheme. 
 Distance relaying scheme. 
Out of these schemes distance relaying is used for transmission line protection, due to their high speed fault clearance compared to other schemes. A distance relay estimates the electrical distance from fault point to relay position and then compared to threshold value which is pre-determined parameters of relay. To determine parameters of relay we need the measuring techniques, which have to ability to detect changes in system configuration, source impedance and fault resistance. So many techniques proposed previously, they are listed below 
 Artificial Neural Network (ANN). 
 Fuzzy Logic & Fuzzy Neuro. 
 Wavelet based systems. 
The aim of this paper is to determine the parameters of relay circuit before employing them in protection system by calculating the threshold values from fault detection, fault classification and fault location with respect to relay point. In this paper we used „Discrete Wavelet Transform‟ which is wavelet based measuring system. 
II. FAULTS IN TRANSMISSION LINE 
Transmission line faults can be categorise into two types, they are 
 Shunt faults. 
 Series faults. 
2.1 Shunt Faults 
Shunt faults are further classified as symmetrical and unsymmetrical faults, symmetrical faults having equal phase voltages i.e. balanced on the other hand unsymmetrical faults has different phase voltages. The unsymmetrical faults are 
 Phase to Ground Fault 
 Phase to Phase Fault. 
 Phase to Phase to Ground Fault. 
2.1.1 Phase to Ground Fault 
The block diagram of single phase to ground fault is shown figure 2.1.1, here „p‟ denotes fault point, „ZF‟ represents fault impedance and „IA‟,‟IB‟,‟IC‟ are respective phase currents. 
RESEARCH ARTICLE OPEN ACCESS
S. Mohaddeesh Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 8( Version 4), August 2014, pp.12-17 
www.ijera.com 13 | P a g e 
The fault current can be given as IF=IA= 3EZ1+Z2+Z3+3ZF Where Z1=Positive sequence impedance Z2=Negative sequence impedance Z0=Zero sequence impedance E=Voltage at fault point. 
2.1.1 Phase to Phase Fault 
The block diagram of phase to phase fault is shown in figure 2.1.2 
The fault current can calculated using below formula IF=IB−IC= √3EZ1+Z2+ZF 
2.1.2 Phase to Phase to Ground Fault 
The block diagram of phase to phase to ground fault is shown in figure 2.1.3. Fault impedance may not be involve. 
The fault current in double line to ground fault is combination all sequence components currents, we can calculate all sequence currents of phase „A‟. The fault current given as follows IF = IB + IC=3IA0 Zero sequence current of phase „A‟ given as IA0= Z1∗IA2−EZ0+3ZF Negative sequence current of Phase „A‟ given as IA2= Z1∗IA1−EZ2 
Positive sequence current of phase „A‟ given as IA1= EZ1+ Z2 Z0+3ZF Z2+Z0+3ZF 
2.1.3 Symmetrical Fault 
Symmetrical fault can also be known as three phase fault with or without ground. The block diagram of three phase fault is shown in figure 2.1.4. 
In symmetrical fault negative sequence and zero sequence components become zero, the fault current is given as follows IF= EZ 
2.2 Series Faults 
In broken conductor faults the load currents can‟t be neglected, as these are the only currents that are flowing in the network. The pre fault load currents are assumed to be balanced, these faults are classified as follows 
 Two conductors open. 
 One conductor open. 
The one conductor open fault is mathematically identical to double phase to ground fault except that the voltages measured. The two conductor open fault mathematically identical to phase to ground fault. 
III. DISCRETE WAVELET TRANSFORM 
The discrete wavelet transform is a multi- resolution analysis and is used extensively in power system applications to analysing transient phenomenon associated to abnormal conditions i.e. Faults. The discrete wavelet transform (DWT) consists only two filters one is low pass filter and other is high pass filter. The output of low pass filter is known as „approximations‟ and denote as A(k) on the other hand output of high pass filter is known as „details‟ and denote as D(k). The block diagram of third order discrete wavelet transform is shown in figure 3.1.
S. Mohaddeesh Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 8( Version 4), August 2014, pp.12-17 
www.ijera.com 14 | P a g e 
We consider only detail coefficients only because low pass filter give output almost same as input i.e. smooth version of input. For DWT some special families of wavelet functions are developed these are commonly known as mother wavelets, these are Daubechies, Haar, Coiflets and Symlets. 
IV. PROPOSED METHODOLOGY 
The proposed methodology uses the Discrete Wavelet Transform for extracting the transient information in the current waveform, which is used to calculate the parameters of Relay Circuit. 
3.1 Waveform Decomposition 
The three phase signals are fed individually through a Discrete Wavelet Transform filter to decompose current waveforms into a series of wavelet components, these wavelet components are very useful for sensing, focussing and classifying the abnormal conditions in transmission line. In this paper we use Daubechies (dB) as mother wavelet, which most commonly used in protection applications and „dB5‟ wavelet is used to decompose the current signal effectively. 
3.2 Fault Detection 
A fault detector must has ability to detect the abnormal condition to dispute an output signal indicating the phase condition. During normal condition both current, voltage waveforms are sinusoidal. Fault signals can be adulterated with different transient components such as exponentially decaying DC offset and high frequency damped oscillations. The coefficients of „Details‟ are used whether the fault is exist or not. If the absolute sum of all detail coefficients greater than the threshold value, fault is exist otherwise no fault in the system. 
Fig.4.2: Algorithm for Fault Detection Let aA, aB, aC are absolute sums of detail coefficients of individual phase currents. Where aA = |sum| of 1st level details of IA aB = |sum| of 1st level details of IB aC = |sum| of 1st level details of IC 푭=풂푨+풂푩+풂푪 If „F‟ greater than the threshold value „T‟, fault will be exist. The steps involved in this algorithm is shown in figure 4.2. 
3.3 Fault Classification 
When the algorithm identify fault in system, after that it classify the type of fault, it can be performed by individual phase threshold values. The flow chart of classification is shown in figure 4.3. The algorithm starts from last step of fault detection. 
Individual Three phase current waveforms 
Decomposition of current waveforms using „DWT‟ filter 
Extract high frequency detail coefficients 
Calculate Absolute sum of detail coefficients „F‟ 
퐹≥푇 
No fault 
Fault (go to classification)
S. Mohaddeesh Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 8( Version 4), August 2014, pp.12-17 
www.ijera.com 15 | P a g e 
Where Ta= Threshold Value of phase „A‟ Tb= Threshold Value of phase „B‟ Tc= Threshold Value of phase „C‟ sA= Details sum of phase „A‟ sB= Details sum of phase „B‟ sC= Details sum of phase „C‟ Tg= Threshold Value of ground 
V. TEST SYSTEM 
The test system was modelled in SIMULINK and various fault conditions are generated. The test system is composed of 220KV transmission lines with length of 300Km connect one end to load section and another end to generating station, a generating station consists of two generator in parallel with capacity of 247MVA, 15.75KV each. The one line diagram of test system is shown in figure 5.1. 
The Simulink model of test model is shown in below figure 5.2. 
The power system transmission parameter are shown in Table-1. The negative sequence parameters are assumed to negligible. 
Power Frequency in Hz 
50 
Transmission line Length in Km 
300 
Positive Sequence Resistance R1, Ω/Km 
0.01273 
Zero Sequence Resistance R0, Ω/Km 
0.3864 
Positive Sequence Inductance L1, H/Km 
0.93e-3 
Zero Sequence Inductance L0, H/Km 
4.12e-3 
Positive Sequence Capacitance C1, F/Km 
12.7e-9 
Zero Sequence Capacitance C0, F/Km 
7.75e-9 
Table-1: Transmission Line Parameters 
VI. SIMULATION RESULTS 
The proposed work was first created in SIMULINK atmosphere. The phase currents are imported to MATLAB atmosphere by workspace, these current signals are given as input to the algorithm which is made exclusively by discrete wavelet transform. The algorithm check the accuracy of Threshold values, further these threshold values used as parameters of Relaying elements. 
F ≥ T 
NO 
NO FAULT 
YES 
aA ≥ Ta 
aB ≥ Tb 
aC ≥ Tc 
|sA+sB+sC|≥ Tg 
Fault in „A‟ 
Fault in „B‟ 
Fault in „C‟ 
With Ground
S. Mohaddeesh Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 8( Version 4), August 2014, pp.12-17 
www.ijera.com 16 | P a g e 
3.4 When no Fault in Power System 
Fig.6.1: Line Voltage & Phase Current 
Fig.6.2: High Freq. Details of A, B, C Currents 
3.5 When Fault in phase ‘A’ with ground 
Fig.6.3: Line Voltage & Phase Current when phase „A‟ fault 
Fig.6.4: High Freq. Details of A, B, C Currents in phase „A‟ Fault 
3.6 When Fault in Phase (B) & Phase (C) 
Fig.6.5: Line Voltage & Phase Current when phase „B‟ & Phase „C‟ fault 
Fig.6.5: High Freq. Details of A, B, C Currents in phase „B‟ & Phase „C‟ Fault The parameters of Relay element is shown in Table-2 and these are nothing but threshold values which are calculated in algorithm. 
VII. CONCLUSION 
For reliable operation of power system, continuity in transmission of electricity from generating station to load centre is must, in general so many faults are occurred in transmission system. In order to maintain stability we have to make use of relay element which disconnects the faulty sections until the fault is cleared, for proper operation of relay we pre-determine the fault levels i.e. parameters of relay. 
Discrete Wavelet Transform have certain advantages over there, vig. Less time required for detection of fault and accuracy concern. REFERENCES [1] K. Sarvanababu, P. Balakrishnan, K. Sathiyasekar, “Transmission line Faults detection, Classification and locating using Discrete Wavelet Transform”. International Conference on Power, Energy and Control (ICPEC) 2013.
S. Mohaddeesh Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 8( Version 4), August 2014, pp.12-17 
www.ijera.com 17 | P a g e 
[2] Sudipta Nath, Priyanjali Mishra, “Wavelet Based Feature Extraction for Classification of Power Quality Disturbances”. International conference on renewable energies and power quality (ICREPQ’11) Las Palmas de gran canaria, 13th to 15th April, 2011. [3] S.A.Shaaban, Takashi Hiyma, “Transmission line Faults classification using wavelet transform”. Proceedings of the 14th international Middle East power system conference (MEPCON”10), December 19-21, 2010. [4] J.Upendar, C.P.gupta, G.K.Singh, “Discrete wavelet transform and Genetic algorithm based fault classification of transmission line”. Fifteenth national power systems conference (NPSC), IIT Bombay, December 2008. [5] Shipli sahu, Dr.A.K.Sharma, “Detection of Fault location in transmission line using Wavelet Transform”. International journal of engineering research and applications, Vol.3, Issue 5, Sep-Oct 2013, pp.149-151. [6] I.J.Nagrath, Kothari, “Power System Analysis”. 4thedition Tata-Mgh hill. [7] “Wavelet theory and Applications”. A Literature study, R.J.E.Merry, DCT 2005.53. BIOGRAPHIES 
S.Mohaddeesh received B.Tech Degree in Electrical & Electronics Engineering from NBKR IST, Vidyanagar in 2011. Currently he is pursuing M.Tech at JNTUA CEP. His research interests include power quality, machine design. 
S.Taj Mahaboob received B.Tech in ECE from MuffakhamJah College of engineering, Hyderabad in 2004 and M.Tech in 2009. Currently she is Ass.Prof. Dept. of ECE, JNTUACE Pulivendula past 10 years. Her Research interests include image processing, DSP.

More Related Content

PPT
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...
PDF
Calculation of short_circuit_currents
PPTX
Fault location for transmission line
PDF
Bus ele tech_lib_short_circuit_current_calculations (1)
PDF
A Novel Study on Bipolar High Voltage Direct Current Transmission Lines Prote...
PDF
Analisis de corto circuito edp01 cálculo de cc
PDF
transmission lineprotection_20100513_web
PDF
DETECTION OF FAULT LOCATION IN TRANSMISSION LINE USING INTERNET OF THINGS (IOT)
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...
Calculation of short_circuit_currents
Fault location for transmission line
Bus ele tech_lib_short_circuit_current_calculations (1)
A Novel Study on Bipolar High Voltage Direct Current Transmission Lines Prote...
Analisis de corto circuito edp01 cálculo de cc
transmission lineprotection_20100513_web
DETECTION OF FAULT LOCATION IN TRANSMISSION LINE USING INTERNET OF THINGS (IOT)

What's hot (20)

PDF
IRJET- Fault Location using Discrete Wavelet Transform for Smart Grid Distrib...
PDF
Symmetrical components in transient regime
PDF
Distance protection scheme for transmission line using back propagation neura...
PDF
Voltage Sag and Swell Identification Using FFT Analysis and Mitigation with DVR
PDF
Consideration of Three Phase Faults on Transmission Line with Distance Protec...
PDF
Double Circuit Transmission Line Protection using Line Trap & Artificial Neur...
PDF
final year project report
PDF
Errors analysis in distance relay readings with presence of facts devices
PDF
F1101043356
PPTX
Ppt fault location
PDF
Artificial Neural Network Based Fault Classifier for Transmission Line Protec...
PDF
ACTIVE vs PASSIVE HARMONICS FILTERS
PDF
Wavelet based analysis for transmission line fault location
PDF
POWER SYSTEM SIMULATION LAB-1 MANUAL (ELECTRICAL - POWER SYSTEM ENGINEERING )
PPT
FAULT DETECTION ON OVERHEAD TRANSMISSION LINE USING ARTIFICIAL NEURAL NET...
PPTX
Fault Location of Overhead Transmission Line
PDF
Fault Location Of Transmission Line
DOCX
circuit explanation of Three phase fault analysis with auto reset for tempora...
PDF
Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance
PDF
IJSRED-V2I2P18
IRJET- Fault Location using Discrete Wavelet Transform for Smart Grid Distrib...
Symmetrical components in transient regime
Distance protection scheme for transmission line using back propagation neura...
Voltage Sag and Swell Identification Using FFT Analysis and Mitigation with DVR
Consideration of Three Phase Faults on Transmission Line with Distance Protec...
Double Circuit Transmission Line Protection using Line Trap & Artificial Neur...
final year project report
Errors analysis in distance relay readings with presence of facts devices
F1101043356
Ppt fault location
Artificial Neural Network Based Fault Classifier for Transmission Line Protec...
ACTIVE vs PASSIVE HARMONICS FILTERS
Wavelet based analysis for transmission line fault location
POWER SYSTEM SIMULATION LAB-1 MANUAL (ELECTRICAL - POWER SYSTEM ENGINEERING )
FAULT DETECTION ON OVERHEAD TRANSMISSION LINE USING ARTIFICIAL NEURAL NET...
Fault Location of Overhead Transmission Line
Fault Location Of Transmission Line
circuit explanation of Three phase fault analysis with auto reset for tempora...
Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance
IJSRED-V2I2P18
Ad

Viewers also liked (20)

PPTX
PPTX
Power Scenario in India
PDF
Energy Sector - 12th Plan (2012 - 2017)
PPT
Indian Energy Sector
PDF
Geological-Structural Setting of Massif and the Levels of Quartz - Sulphide M...
PDF
Micro CT settings for caries detection: how to optimize
PDF
Ground Improvement of Dune Sand Fields For The Purpose of Moisture Retention
PDF
Characterization of Wastewater in Rajouri Town, Jammu And Kashmir, India
PDF
N046047780
PDF
Hack Recognition In Wireless Sensor Network
PDF
P4806112122
PDF
The influence of the manganese citrates, obtained using aquananotechnologies,...
PDF
N046068589
PDF
Towards Improving Crash Data Management System in Gulf Countries
PDF
Structure Analysis of a Turbocharger Compressor Wheel Using FEA
PDF
Peer-to-Peer content distribution using automatically recombined fingerprints
PDF
A Stochastic Model for the Progression of Chronic Kidney Disease
PDF
Size and Time Estimation in Goal Graph Using Use Case Points (UCP): A Survey
PDF
Efficient video compression using EZWT
PDF
N480690102
Power Scenario in India
Energy Sector - 12th Plan (2012 - 2017)
Indian Energy Sector
Geological-Structural Setting of Massif and the Levels of Quartz - Sulphide M...
Micro CT settings for caries detection: how to optimize
Ground Improvement of Dune Sand Fields For The Purpose of Moisture Retention
Characterization of Wastewater in Rajouri Town, Jammu And Kashmir, India
N046047780
Hack Recognition In Wireless Sensor Network
P4806112122
The influence of the manganese citrates, obtained using aquananotechnologies,...
N046068589
Towards Improving Crash Data Management System in Gulf Countries
Structure Analysis of a Turbocharger Compressor Wheel Using FEA
Peer-to-Peer content distribution using automatically recombined fingerprints
A Stochastic Model for the Progression of Chronic Kidney Disease
Size and Time Estimation in Goal Graph Using Use Case Points (UCP): A Survey
Efficient video compression using EZWT
N480690102
Ad

Similar to Power System’stransmission Line Relaying Improvement Using Discrete Wavelet Transform (20)

PDF
Wavelet based double line and double line -to- ground fault discrimination i...
PDF
Wavelet based double line and double line -to- ground fault discrimination i...
PDF
Wavelet based double line and double line -to- ground fault discrimination i...
PDF
Moshtagh new-approach-ieee-2006
PDF
Wavelet based detection and location of faults in 400kv, 50km Underground Po...
PDF
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
PDF
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
PDF
Z35149151
PDF
Wavelet Based Fault Detection, Classification in Transmission System with TCS...
PDF
40220140507004
PDF
40220140507004
PDF
Transient Monitoring Function based Fault Classifier for Relaying Applications
PDF
A Time-Frequency Transform Based Fault Detectionand Classificationof STATCOM ...
PDF
Detection of Transmission Line Faults by Wavelet Based Transient Extraction
PDF
Differential equation fault location algorithm with harmonic effects in power...
PDF
Wavelet energy moment and neural networks based particle swarm optimisation f...
PDF
IRJET - Transmission Line Fault Classification using DWT
PPTX
Presentation on FAULT CLASSIFICATION.pptx
PDF
IRJET- Wavelet Decomposition along with ANN used for Fault Detection
PDF
A New Approach for Classification of Fault in Transmission Line with Combinat...
Wavelet based double line and double line -to- ground fault discrimination i...
Wavelet based double line and double line -to- ground fault discrimination i...
Wavelet based double line and double line -to- ground fault discrimination i...
Moshtagh new-approach-ieee-2006
Wavelet based detection and location of faults in 400kv, 50km Underground Po...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
Z35149151
Wavelet Based Fault Detection, Classification in Transmission System with TCS...
40220140507004
40220140507004
Transient Monitoring Function based Fault Classifier for Relaying Applications
A Time-Frequency Transform Based Fault Detectionand Classificationof STATCOM ...
Detection of Transmission Line Faults by Wavelet Based Transient Extraction
Differential equation fault location algorithm with harmonic effects in power...
Wavelet energy moment and neural networks based particle swarm optimisation f...
IRJET - Transmission Line Fault Classification using DWT
Presentation on FAULT CLASSIFICATION.pptx
IRJET- Wavelet Decomposition along with ANN used for Fault Detection
A New Approach for Classification of Fault in Transmission Line with Combinat...

Recently uploaded (20)

PPTX
Foundation to blockchain - A guide to Blockchain Tech
DOCX
573137875-Attendance-Management-System-original
PDF
Well-logging-methods_new................
PPTX
Fundamentals of Mechanical Engineering.pptx
PPTX
Current and future trends in Computer Vision.pptx
PPTX
UNIT 4 Total Quality Management .pptx
PPT
Mechanical Engineering MATERIALS Selection
PPT
introduction to datamining and warehousing
PDF
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
PDF
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PPT
Project quality management in manufacturing
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PPTX
Safety Seminar civil to be ensured for safe working.
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PDF
Categorization of Factors Affecting Classification Algorithms Selection
PPTX
Internet of Things (IOT) - A guide to understanding
PPTX
Sustainable Sites - Green Building Construction
PDF
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
Foundation to blockchain - A guide to Blockchain Tech
573137875-Attendance-Management-System-original
Well-logging-methods_new................
Fundamentals of Mechanical Engineering.pptx
Current and future trends in Computer Vision.pptx
UNIT 4 Total Quality Management .pptx
Mechanical Engineering MATERIALS Selection
introduction to datamining and warehousing
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
Project quality management in manufacturing
Embodied AI: Ushering in the Next Era of Intelligent Systems
Safety Seminar civil to be ensured for safe working.
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
UNIT-1 - COAL BASED THERMAL POWER PLANTS
Categorization of Factors Affecting Classification Algorithms Selection
Internet of Things (IOT) - A guide to understanding
Sustainable Sites - Green Building Construction
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT

Power System’stransmission Line Relaying Improvement Using Discrete Wavelet Transform

  • 1. S. Mohaddeesh Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 8( Version 4), August 2014, pp.12-17 www.ijera.com 12 | P a g e Power System’stransmission Line Relaying Improvement Using Discrete Wavelet Transform S. Mohaddeesh*, S. Taj Mahaboob** *(PG Scholar, DE & CS, JNTUACE Pulivendula, Andhra Pradesh) ** (Asst. Professor, Dept. of ECE, JNTUACE Pulivendula, Andhra Pradesh) ABSTRACT Transmission line is a path between the generating station and load(Industries & Domestic). These lines are several kilometres and always attracted towards faults. These Faults are Phase to Ground (P-G), Phase to Phase (P-P), Phase to Phase to Ground (P-P-G) and Symmetrical Fault (P-P-PP-P-P-G).In order to protect the power system, faults should be cleared within stipulated time. Relay plays a key role in power system protection, before employing them in system, their parameters should be pre-determined.The proposed system uses Discrete Wavelet Transform to determine the fault levels in power system. It is used to extract the hidden factors i.e. Transients, from the faulty current signals by performing decomposition at different levels. Test system is modelled and fault signals are imported to workspace and test the reliability of the algorithm. The proposed system modelled in MATLABSIMULINK to detect, classify and locate all the possible faults in the transmission line in the power system which are nothing but parameters of relays. Keywords – Discrete Wavelet Transform, Faults, Relay Parameters, Transients, Transmission Line. I. INTRODUCTION Electricity is very important component to universe. Power System is a system which generate electricity and dispatch to the loads these are generally industries and households. Power System consists Generating stations, Transmission lines and Load Centres. Transmission line interconnects the generating station to different load centres, they run over several kilometres and fascinated to faults, and to maintain continuity of operation we should clear the faults within short period. Relay plays main role in protection of transmission line, and assimilated to detect the abnormal condition in the system which notice faults and isolate the faulty part from the power system with negligible disturbance in the system. There are several relaying schemes are available they are  Overcurrent relaying scheme.  Differential relaying scheme.  Distance relaying scheme. Out of these schemes distance relaying is used for transmission line protection, due to their high speed fault clearance compared to other schemes. A distance relay estimates the electrical distance from fault point to relay position and then compared to threshold value which is pre-determined parameters of relay. To determine parameters of relay we need the measuring techniques, which have to ability to detect changes in system configuration, source impedance and fault resistance. So many techniques proposed previously, they are listed below  Artificial Neural Network (ANN).  Fuzzy Logic & Fuzzy Neuro.  Wavelet based systems. The aim of this paper is to determine the parameters of relay circuit before employing them in protection system by calculating the threshold values from fault detection, fault classification and fault location with respect to relay point. In this paper we used „Discrete Wavelet Transform‟ which is wavelet based measuring system. II. FAULTS IN TRANSMISSION LINE Transmission line faults can be categorise into two types, they are  Shunt faults.  Series faults. 2.1 Shunt Faults Shunt faults are further classified as symmetrical and unsymmetrical faults, symmetrical faults having equal phase voltages i.e. balanced on the other hand unsymmetrical faults has different phase voltages. The unsymmetrical faults are  Phase to Ground Fault  Phase to Phase Fault.  Phase to Phase to Ground Fault. 2.1.1 Phase to Ground Fault The block diagram of single phase to ground fault is shown figure 2.1.1, here „p‟ denotes fault point, „ZF‟ represents fault impedance and „IA‟,‟IB‟,‟IC‟ are respective phase currents. RESEARCH ARTICLE OPEN ACCESS
  • 2. S. Mohaddeesh Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 8( Version 4), August 2014, pp.12-17 www.ijera.com 13 | P a g e The fault current can be given as IF=IA= 3EZ1+Z2+Z3+3ZF Where Z1=Positive sequence impedance Z2=Negative sequence impedance Z0=Zero sequence impedance E=Voltage at fault point. 2.1.1 Phase to Phase Fault The block diagram of phase to phase fault is shown in figure 2.1.2 The fault current can calculated using below formula IF=IB−IC= √3EZ1+Z2+ZF 2.1.2 Phase to Phase to Ground Fault The block diagram of phase to phase to ground fault is shown in figure 2.1.3. Fault impedance may not be involve. The fault current in double line to ground fault is combination all sequence components currents, we can calculate all sequence currents of phase „A‟. The fault current given as follows IF = IB + IC=3IA0 Zero sequence current of phase „A‟ given as IA0= Z1∗IA2−EZ0+3ZF Negative sequence current of Phase „A‟ given as IA2= Z1∗IA1−EZ2 Positive sequence current of phase „A‟ given as IA1= EZ1+ Z2 Z0+3ZF Z2+Z0+3ZF 2.1.3 Symmetrical Fault Symmetrical fault can also be known as three phase fault with or without ground. The block diagram of three phase fault is shown in figure 2.1.4. In symmetrical fault negative sequence and zero sequence components become zero, the fault current is given as follows IF= EZ 2.2 Series Faults In broken conductor faults the load currents can‟t be neglected, as these are the only currents that are flowing in the network. The pre fault load currents are assumed to be balanced, these faults are classified as follows  Two conductors open.  One conductor open. The one conductor open fault is mathematically identical to double phase to ground fault except that the voltages measured. The two conductor open fault mathematically identical to phase to ground fault. III. DISCRETE WAVELET TRANSFORM The discrete wavelet transform is a multi- resolution analysis and is used extensively in power system applications to analysing transient phenomenon associated to abnormal conditions i.e. Faults. The discrete wavelet transform (DWT) consists only two filters one is low pass filter and other is high pass filter. The output of low pass filter is known as „approximations‟ and denote as A(k) on the other hand output of high pass filter is known as „details‟ and denote as D(k). The block diagram of third order discrete wavelet transform is shown in figure 3.1.
  • 3. S. Mohaddeesh Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 8( Version 4), August 2014, pp.12-17 www.ijera.com 14 | P a g e We consider only detail coefficients only because low pass filter give output almost same as input i.e. smooth version of input. For DWT some special families of wavelet functions are developed these are commonly known as mother wavelets, these are Daubechies, Haar, Coiflets and Symlets. IV. PROPOSED METHODOLOGY The proposed methodology uses the Discrete Wavelet Transform for extracting the transient information in the current waveform, which is used to calculate the parameters of Relay Circuit. 3.1 Waveform Decomposition The three phase signals are fed individually through a Discrete Wavelet Transform filter to decompose current waveforms into a series of wavelet components, these wavelet components are very useful for sensing, focussing and classifying the abnormal conditions in transmission line. In this paper we use Daubechies (dB) as mother wavelet, which most commonly used in protection applications and „dB5‟ wavelet is used to decompose the current signal effectively. 3.2 Fault Detection A fault detector must has ability to detect the abnormal condition to dispute an output signal indicating the phase condition. During normal condition both current, voltage waveforms are sinusoidal. Fault signals can be adulterated with different transient components such as exponentially decaying DC offset and high frequency damped oscillations. The coefficients of „Details‟ are used whether the fault is exist or not. If the absolute sum of all detail coefficients greater than the threshold value, fault is exist otherwise no fault in the system. Fig.4.2: Algorithm for Fault Detection Let aA, aB, aC are absolute sums of detail coefficients of individual phase currents. Where aA = |sum| of 1st level details of IA aB = |sum| of 1st level details of IB aC = |sum| of 1st level details of IC 푭=풂푨+풂푩+풂푪 If „F‟ greater than the threshold value „T‟, fault will be exist. The steps involved in this algorithm is shown in figure 4.2. 3.3 Fault Classification When the algorithm identify fault in system, after that it classify the type of fault, it can be performed by individual phase threshold values. The flow chart of classification is shown in figure 4.3. The algorithm starts from last step of fault detection. Individual Three phase current waveforms Decomposition of current waveforms using „DWT‟ filter Extract high frequency detail coefficients Calculate Absolute sum of detail coefficients „F‟ 퐹≥푇 No fault Fault (go to classification)
  • 4. S. Mohaddeesh Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 8( Version 4), August 2014, pp.12-17 www.ijera.com 15 | P a g e Where Ta= Threshold Value of phase „A‟ Tb= Threshold Value of phase „B‟ Tc= Threshold Value of phase „C‟ sA= Details sum of phase „A‟ sB= Details sum of phase „B‟ sC= Details sum of phase „C‟ Tg= Threshold Value of ground V. TEST SYSTEM The test system was modelled in SIMULINK and various fault conditions are generated. The test system is composed of 220KV transmission lines with length of 300Km connect one end to load section and another end to generating station, a generating station consists of two generator in parallel with capacity of 247MVA, 15.75KV each. The one line diagram of test system is shown in figure 5.1. The Simulink model of test model is shown in below figure 5.2. The power system transmission parameter are shown in Table-1. The negative sequence parameters are assumed to negligible. Power Frequency in Hz 50 Transmission line Length in Km 300 Positive Sequence Resistance R1, Ω/Km 0.01273 Zero Sequence Resistance R0, Ω/Km 0.3864 Positive Sequence Inductance L1, H/Km 0.93e-3 Zero Sequence Inductance L0, H/Km 4.12e-3 Positive Sequence Capacitance C1, F/Km 12.7e-9 Zero Sequence Capacitance C0, F/Km 7.75e-9 Table-1: Transmission Line Parameters VI. SIMULATION RESULTS The proposed work was first created in SIMULINK atmosphere. The phase currents are imported to MATLAB atmosphere by workspace, these current signals are given as input to the algorithm which is made exclusively by discrete wavelet transform. The algorithm check the accuracy of Threshold values, further these threshold values used as parameters of Relaying elements. F ≥ T NO NO FAULT YES aA ≥ Ta aB ≥ Tb aC ≥ Tc |sA+sB+sC|≥ Tg Fault in „A‟ Fault in „B‟ Fault in „C‟ With Ground
  • 5. S. Mohaddeesh Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 8( Version 4), August 2014, pp.12-17 www.ijera.com 16 | P a g e 3.4 When no Fault in Power System Fig.6.1: Line Voltage & Phase Current Fig.6.2: High Freq. Details of A, B, C Currents 3.5 When Fault in phase ‘A’ with ground Fig.6.3: Line Voltage & Phase Current when phase „A‟ fault Fig.6.4: High Freq. Details of A, B, C Currents in phase „A‟ Fault 3.6 When Fault in Phase (B) & Phase (C) Fig.6.5: Line Voltage & Phase Current when phase „B‟ & Phase „C‟ fault Fig.6.5: High Freq. Details of A, B, C Currents in phase „B‟ & Phase „C‟ Fault The parameters of Relay element is shown in Table-2 and these are nothing but threshold values which are calculated in algorithm. VII. CONCLUSION For reliable operation of power system, continuity in transmission of electricity from generating station to load centre is must, in general so many faults are occurred in transmission system. In order to maintain stability we have to make use of relay element which disconnects the faulty sections until the fault is cleared, for proper operation of relay we pre-determine the fault levels i.e. parameters of relay. Discrete Wavelet Transform have certain advantages over there, vig. Less time required for detection of fault and accuracy concern. REFERENCES [1] K. Sarvanababu, P. Balakrishnan, K. Sathiyasekar, “Transmission line Faults detection, Classification and locating using Discrete Wavelet Transform”. International Conference on Power, Energy and Control (ICPEC) 2013.
  • 6. S. Mohaddeesh Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 8( Version 4), August 2014, pp.12-17 www.ijera.com 17 | P a g e [2] Sudipta Nath, Priyanjali Mishra, “Wavelet Based Feature Extraction for Classification of Power Quality Disturbances”. International conference on renewable energies and power quality (ICREPQ’11) Las Palmas de gran canaria, 13th to 15th April, 2011. [3] S.A.Shaaban, Takashi Hiyma, “Transmission line Faults classification using wavelet transform”. Proceedings of the 14th international Middle East power system conference (MEPCON”10), December 19-21, 2010. [4] J.Upendar, C.P.gupta, G.K.Singh, “Discrete wavelet transform and Genetic algorithm based fault classification of transmission line”. Fifteenth national power systems conference (NPSC), IIT Bombay, December 2008. [5] Shipli sahu, Dr.A.K.Sharma, “Detection of Fault location in transmission line using Wavelet Transform”. International journal of engineering research and applications, Vol.3, Issue 5, Sep-Oct 2013, pp.149-151. [6] I.J.Nagrath, Kothari, “Power System Analysis”. 4thedition Tata-Mgh hill. [7] “Wavelet theory and Applications”. A Literature study, R.J.E.Merry, DCT 2005.53. BIOGRAPHIES S.Mohaddeesh received B.Tech Degree in Electrical & Electronics Engineering from NBKR IST, Vidyanagar in 2011. Currently he is pursuing M.Tech at JNTUA CEP. His research interests include power quality, machine design. S.Taj Mahaboob received B.Tech in ECE from MuffakhamJah College of engineering, Hyderabad in 2004 and M.Tech in 2009. Currently she is Ass.Prof. Dept. of ECE, JNTUACE Pulivendula past 10 years. Her Research interests include image processing, DSP.